2 Zone Conventional Fire Alarm Control Panel

0 Reviews

Condition : New Warranty: YES
Country of shipping : China
Request for quotation
Payment options

Product Specification

Brand ANKA
Condition New
Warranty YES
Power Source Electric

Product Description


Products model: AJ-S1002

Specification

Feature

1. 2 zone fire panel, each zone can connect 25pcs 2 wire devices. Each zone cable max length is 5km.

2. Fire accessories optional: smoke detector, heat detector, pull station, etc. 

 

Technical specification

Item Describe
Primary  AC 120VAC 50/60 Hz Power supply rating
240VAC 50/60 Hz
Power supply rating  2 Amps @ 24VDC
Maximum Battery Charging Current  0.98 Amps @ 26VDC
Initiating Device Circuits 2 Zones  Alarm Zone 2
Normal Initiating Operating Voltage  23VDC, Maximum 26VDC, regulated
Normal Quiescent Current (normal status)  <50mA
Alarm Current (not include the others) 
Short Circuit Initiating Current (per zone)  35mA Maximum
Maximum Initiating Resistance (per zone)  10 ohms
Initiating End-of-Line Resistor  4K7 ohms, 1/2W 5%
Standby Detector Current (per zone)  4mA maximum
Maximum Detector Count (per zone)  30 detectors
Initiating Cabling Type  18AWG Twisted Shielded pair (14 – 18 AWG)
Detector Base Impedance  430 ohms
Notification Appliance Circuits  1 NACs, Special Application
Maximum NAC Current Rating  1 Amp maximum per circuit
NAC Operating Voltage  26VDC Nominal, 30VDC Maximum
NAC End-of-line Resistor  1N4007 Diode
FAULT Relay rating  2A & 30VAC, resistive
Alarm( Auxiliary ) Relay rating  2A & 30VAC, resistive
CP1002M (Master alarm panel)  With power supply and digital display
CP1002S (Slave alarm panel)  With power supply ,without digital display
CP1002W(Slave alarm panel)  With power supply, without digital display