Product Specification
| Brand | TOPRIE |
Product Descriptions
3 phase 3 wire system, 3 phase 4 wire system | ||
Input voltage | Range | AC3*220V ~380V |
| Power consumption | <1VA(per phase) | |
| Overload | Continuous:1.2 times Instant:2 times per 10s | |
| Resistance | ≥300KΩ | |
| Accuracy | RMS measurement Accuracy level:0.5 | |
Input current | Range | AC 0.025A~5A |
| Overload | Continuous:1.2 times Instant:10 times per 10s | |
| Power consumption | 0.4VA(per phase) | |
| Resistance | <20mΩ | |
| Accuracy | RMS measurement Accuracy level:0.5 | |
| Frequency Range | 40Hz~65Hz Accuracy:0.1Hz | |
| Power | Active power,reactive power,apparent power Accuracy level:0.5 | |
| Display | LCD TFT large display screen | |
| Power supply | AC100V~240V(100V~265V) | |
| Power supply consumption | ≤7VA | |
| Communication | RS485 adopt MODBUS-RTU protocol | |
| Pulse output | 3 channel power pulse output pulse constant 3200imp/kWh | |
| Switch input(optional) | 4 channel input (wet contact method),support remote function | |
| Analog output(optional) | 1 channel analog transducer output,4-20mA(DC) with load<500Ω | |
| Alarm output(optional) | 2 channel switch output AC 250V/3A or DC 30V/5A support remote function | |
| Operation environment | Temperature:-10℃~50℃ humidity:<85%RH no corrosive gas altitude≤2500m | |
| Storage environment | -25℃~70℃ | |
| Isolation withstand voltage | Signal input and power supply 1600VAC, Signal input and output 1600VAC power supply and transmit output,485 interface,DI interface,pulse output interface≥DC200VAC | |
| Insulation | Input,output, power supply shell>5MΩ | |
| Dimension | 96*96*108mm | |
| Weight | 270g | |
| Measurement standard | IEC62053-22,GB/T17215.322-2018 | |
| Environment standard | IEC60068-2 | |
| Safety standard | IEC61010-1 UL61010-1 | |
| Electromagnetic compatible Standard | IEC61000-4/2-3-4-5-6-8-11,CISPR 22 | |
| Appearance standard | DIN43700,ANSIC 39.1 |