Product Specification
HELUKABEL | |
New | |
YES |
Product Descriptions
Technical data
- Power and control cable to
DIN VDE 0276 part 603,
HD 603 S1 and IEC 60502,
7 cores and above to DIN VDE 0276
part 627, HD 627 S1 and IEC 60502 - Temperature range
flexing -5°C to +50°C
fixed installation -40°C to +70°C - Permissible operating temperature
at conductor +90°C - Permissible short circuit temperature
(short circuit duration max. 5 s)
+250°C - Nominal voltage U0/U 0,6/1 kV
- Test voltage 4 kV
- Max. permissible tensile stress
with cable grip at conductor
50 N/mm² - Minimum bending radius
12x cable Ø
Cable structure
- Bare copper conductor, to
DIN VDE 0295 cl.1 or cl.2, single-wire
or multi-wire, BS 6360 cl.1 or cl.2,
IEC 60228 cl.1 or cl.2 - Core insulation of cross-linked
polyethylene (XLPE)
compound type DIX3 to HD 603 S1 - Core identification to DIN VDE 0293-308
- Cores stranded in concentric layers
- Filling compound
- Concentric conductor, inner layer of round
bare copper wires, outer layer of copper
tape as counter helix - Outer sheath of PVC
compound type DMV6 to HD 603 S1 - Sheath colour: black